Tor AHU Panel product

DDC Panels

Tor AHU Panel

A DDC panel for controlling and monitoring Air Handling Unit. It controls the chilled water valve and fan, monitors every trip and filter alarm, and reports to Tor Shield.

What it runs

  • Supply or return air temperature control by modulating the chilled water valve
  • Fan speed through the VFD, on a 0–10 V signal
  • Start/stop on schedule or on command from Tor Shield
  • Fan status, trip and auto/manual feedback
  • Filter and fault alarms pushed to the Tor Shield dashboard and phone

What's inside

  • Tor Saturn 521 controller
  • Tor Jupiter gateway (812 or 511 GSM)
  • 12 V SMPS
  • 2-pole 16 A MCB
  • 230 V AC and 12 V DC interposing relays on 8-pin bases
  • 12-pin plug-in field connector

Choose your variant

GSM specifications
GatewayJupiter 511 GSM
Total I/O30 (8 DI, 12 DO, 8 AI, 2 AO)
Field protocolModbus RS485, BLE
Backhaul4G/GSM, no IT network needed
DeploymentCloud
Best forRetrofits, remote AHU rooms, sites where IT will not open a port

Typical point map

SignalCountTypical use
Analog outputs (0–10 V)2Chilled water valve, VFD speed
Analog inputs8Supply air temp, return air temp, chilled water temp, duct pressure
Digital inputs8Fan status, VFD trip, filter alarm, auto/manual
Digital outputs12Fan start/stop, alarms, auxiliary loads

The GSM variant adds the Jupiter 511's 4 DI, 4 DO and 4 AI for extra sensors or a second fan.