Tor Shield Integrated Building Management System

HVAC Optimization with Tor SOLACE

Tor SOLACE, an add-on to Tor Shield IBMS, runs a continuous optimisation loop across chillers, cooling towers, pumps and AHU fans, within the comfort limits you set. It minimises total HVAC power by 15–30%.

Run the savings calculator

Case study · Achieved with Tor Shield

7% energy savings, reduced downtime, and a leaner operations team: how Tor Shield IBMS delivered at The St. Regis Goa Resort

Read case study ›

Trusted by industry leaders

St. Regis
Hyatt
Westin
Panchshil
Bombay Stock Exchange
Phoenix
IKEA
Smartworks

The interdependency premium

Why the whole plant saves more than its parts

Every lever in a chilled water plant saves energy in one place and spends it in another.

Warmer chilled water

Saves

Cuts chiller power about 2.5–3% per 1°C.

But

Pumps and AHU fans must move more water and air.

Cooler condenser water

Saves

Cuts chiller power about 2.5–3% per 1°C.

But

Tower fans must run faster.

Slower pumps

Saves

A 20% speed cut saves about half the pump's power.

But

Too little flow starves coils and chillers.

The lowest total plant power sits at a point no single machine would choose on its own. Tor SOLACE finds it by minimising one number:

Total plant kW = chillers + chilled water pumps + condenser water pumps + tower fans + AHU fans

Optimise each machine alone and you leave savings behind. We call that gap the interdependency premium.

Traditional control vs Tor SOLACE

What changes when the HVAC system is optimised as one

Most buildings run their HVAC subsystems on independent setpoints. Plant optimisers that coordinate them usually depend on an additional layer of instrumentation. Tor SOLACE coordinates the full system using the data Tor Shield already collects.

Control objective

Conventional BMS
Each subsystem holds its own setpoint
Instrumentation-heavy optimisers
Minimise total plant kW
Tor SOLACE
Minimise total HVAC kW, AHU fans included

Setpoints

Conventional BMS
Fixed or time-scheduled
Instrumentation-heavy optimisers
Dynamic
Tor SOLACE
Recalculated continuously as load and wet bulb change

Coordination

Conventional BMS
None: subsystems work against each other
Instrumentation-heavy optimisers
Typically the plant room only
Tor SOLACE
Plant room and air side, as one system

Coil-level visibility

Conventional BMS
None
Instrumentation-heavy optimisers
Energy valve or BTU meter on each AHU
Tor SOLACE
Coil Performance Index from existing ΔT and valve signals

Instrumentation

Conventional BMS
Basic
Instrumentation-heavy optimisers
Additional instrumentation package
Tor SOLACE
Runs on Tor Shield's standard instrumentation

Tor SOLACE is an add-on to Tor Shield IBMS and runs on the controllers, meters and sensors that Tor Shield installs.

The SOLACE optimisation loop

How Tor SOLACE runs the plant as one system

  1. 01

    Measure

    Tor's DDC panels, meters and sensors read power, temperatures, pressure, valve positions and wet bulb across the plant, adding metering where it's missing.

  2. 02

    Calculate

    It computes plant-room IKW and total HVAC kW, AHU fans included.

  3. 03

    Act

    It stages chillers, resets chilled and condenser water setpoints, and sets pump, fan and valve positions to minimise total kW within the comfort limits you set.

  4. 04

    Verify

    After every change it tracks IKW against a weather-normalised baseline, so a setting that stops paying gets caught.

Estimate your savings

What could your building save?

Use our savings calculator for your hotel, hospital, mall or commercial building. Enter your chillers, pumps, cooling towers and AHUs to get a savings range for each subsystem and your plant's current IKW.

Works with your plant

Works with the plant you already have

Any chiller brand

Integrates multi-brand chillers over BACnet and Modbus.

No rip-and-replace

Retrofits existing plants. We add the control layer and keep your equipment.

Cloud, on-premises or hybrid

You choose where the platform runs.

Safety interlocks

Valves, pumps and compressors start and stop in the correct order every time. Configurable interlocks stop operation outside the limits you set.

Manual override

Operators can switch any asset between Auto and Manual from the dashboard.

FAQ

Frequently Asked Questions

Do I need VFDs?+

No. Chiller sequencing and setpoint reset work on fixed-speed equipment. VFDs on pumps and tower fans add the speed savings, so savings are smaller without them.

Which chiller brands do you work with?+

Any brand that communicates over BACnet or Modbus.

Will it affect my chiller warranty?+

No. Tor Shield runs your chillers, pumps, cooling towers and AHUs within the operating limits their manufacturers set: flow, temperature, run time and restart intervals. It optimises inside those limits, never around them, so your equipment runs the way its manufacturer intended.

Can our operators override it?+

Yes. Any asset can be switched to Manual from the dashboard, and configurable interlocks stop operation outside the limits you set.

Does it need the cloud?+

No. It runs in the cloud, on-premises or as a hybrid.

How long does deployment take?+

It depends on plant size and how much instrumentation is already in place.

Who owns the data?+

You do. Your plant data belongs to you, and you can export it at any time.

Is remote control secure?+

Yes. Connections are encrypted, every user has role-based access, and every command is logged. On-premises deployments can run with no internet connection.